Generic motor Error Code Motor Overload / Overload Relay Trip

Motor Overload Relay Tripped

What does Motor Overload / Overload Relay Trip mean?

Motor overload relay (thermal or electronic) detected current above rated FLA, shutting down motor.

Common causes

Diagnostic & testing steps

  1. 1. Allow motor to cool 10-15 minutes before resetting
  2. 2. Check overload relay trip current setting vs motor nameplate FLA
  3. 3. Measure running current on all phases with clamp meter
  4. 4. Compare to FLA: should not exceed 100% FLA continuously
  5. 5. On 3-phase: check for voltage imbalance >3% between phases
  6. 6. Check driven load for mechanical binding or jam
  7. 7. Test motor insulation with Megger: >1M ohm phase to ground acceptable

Tools required

OEM parts & part numbers

Overload Relay, Motor Starter, Contactors

Part numbers: 3RU2116-1AB0, LRD10C

Safety warning

⚠️ LOCK OUT / TAG OUT: De-energize and lock out motor control panel before accessing motor or starter. Store energy (capacitors) may remain. Verify voltage is zero with meter before working.