What does 31 mean?
Compressor discharge temperature is critically high. Compressor is at risk of damage.
Common causes
- Low refrigerant
- Compressor valve failure
- Liquid slug in compressor
- High ambient temperature operation
Diagnostic & testing steps
- 1. Check discharge temperature: should be below 225°F
- 2. Check suction superheat: normal is 10-20°F
- 3. Check subcooling: normal is 10-15°F
- 4. Listen for abnormal compressor sounds
- 5. Measure compressor amp draw vs nameplate RLA
Tools required
- Manifold gauge set
- Temperature clamp probe
- Amp clamp
OEM parts & part numbers
Compressor, Refrigerant (R-410A)
Part numbers: 5F40NCA036000
Safety warning
⚠️ COMPRESSOR HAZARD: High discharge temps can cause catastrophic compressor failure. Shut down immediately if overheating.